top of page

Diesel fuel polishing for standby generators

6 days ago
2 min read

A standby generator may sit for months between runs, but when the mains fail it has to start and carry the load at once. Very often, when it does not, the cause is the fuel: water, sludge and microbial growth in a tank that has not been turned over.

Why stored diesel goes bad

  • Water: condensation from the air the tank breathes, rain through vents and fill points, and water delivered with the fuel collect at the bottom of the tank.

  • Microbial growth: bacteria and fungi live at the boundary between the water layer and the fuel, forming dark slime that blocks filters.

  • Oxidation: fuel slowly oxidises in storage, especially biodiesel blends, forming gums and sediment.

  • Sediment: rust and dirt from the tank and the delivery chain settle and are stirred up when the generator starts.

The result is blocked fuel filters, worn injectors and engines that stop under load just when they are needed.

What fuel polishing does

A fuel polishing unit draws fuel from the bottom of the tank, where water and sediment collect, and passes it through:

  1. a particle pre-filter, which removes sediment and sludge;

  2. a coalescer and water separator, which merges fine water droplets so they fall to a sump and are drained;

  3. a fine filter, before the clean, dry fuel is returned to the tank.

Running on a timer, it turns the tank volume over regularly so water and sludge never build up.

Good practice for standby fuel

  • Drain water from tank bottoms regularly, and fit an automatic drain where the site is unattended.

  • Fit desiccant breathers on tank vents to cut condensation.

  • Test the fuel for water, sediment and microbial growth at least once a year.

  • Polish the fuel continuously or on a timer, rather than waiting for a problem.

Vens fuel polishing

The Vens VH-FPU diesel fuel polishing unit combines pre-filter, coalescer, water separator and fine filter on a skid, wall frame or trolley, with timer or continuous operation, a water sump with sight glass and optional automatic drain and water-in-fuel alarm. For tank vents, see the VH-DSB desiccant breather.

Tell us the tank sizes, the fuel and how often it is used, and we will size the unit.

Comments